Master FC400 series static Frequency Converters are available from 30 to 125 kVA, with 50 or 60 Hz input and 400 Hz output.
Power Range: 30 – 125 kVA
3:3
Master FC400 series static Frequency Converters are available from 30 to 125 kVA, with 50 or 60 Hz input and 400 Hz output. The result of extensive experience acquired in the UPS industry, the Master FC400 series is distinguished by the use of technologically advanced components and for excellent reliability, ease of maintenance and ease of operation.
The Master FC400 series uses double conversion technology (VFI SS 111 voltage and frequency independent compliant with IEC EN 62040-3), with an integrated output transformer to ensure the galvanic isolation of the load from mains disturbances under all conditions.
The output voltage is 208 V threephase (adjustable 200-215 V). Thanks to high frequency IGBT technology and digital control, Master FC400 Frequency Converters are ideal for airport, military and naval applications.
Models | MFC 125 |
INPUT | |
Voltage | 380 / 400 / 415 V three-phase |
Voltage tolerance | 400 V ±20% @ full load |
Frequency tolerance | 45 ÷ 65 Hz |
Current distorsion | <5% C (HC Version) |
Soft start | 0 – 100% in 120 sec. configurable |
OUTPUT and INVERTER OUTPUT | |
Rated power | 125000 VA |
Active power | 100000 W |
Number phases | 3 |
Crest factor (Ipeak/Irms) | 3 : 1 |
Waveform | sinusoidal |
Static stability | ±1% |
Dynamic stability | ±5% |
Frequency | 400 Hz |
Voltage distortion with non-linear load | <4% |
Voltage distortion with linear load | <3% |
Overload | 110% for 60 min.; 125% for 10 min.; 150% for 1 min. |
ENVIRONMENTAL | |
Color | Light gray RAL 7035 |
Communication | Double RS232 + remote contacts + 2 slots for communications interface |
Protection rating | IP20 |
AC/AC efficiency | up to 92% |
Noise (at 1 m) | 72 dBA |
Operating temperature | 0 °C – 40 °C (50°C @ 75% load) |
Relative humidity | 5-95% non-condensing |
Standards | European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility — Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant — Classification in accordance with IEC 62040-3 VFI – SS – 111 |
DATA | |
Weight | 590 kg |
Dimensions (h w d) | 1900 x 800 x 800 mm |