Master Industrial MIM 30

Master Industrial MIM 30

DC BUS 220 Vdc

Ideal for industrial installations

Master Industrial series UPS provide maximum protection and power quality for any type of load, especially industrial applications, such as manufacturing
and petrochemical processes, electrical distribution and power plants. Master Industrial is an on-line double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with input and output isolation transformers.

 

Technical specifications of the model MIM 30
Models MIM 30
INPUT  
Rated power 30000 VA
Voltage 400 Vac three-phase Vac
Voltage tolerance ± 20%
Frequency 50/60 Hz with autorange
Frequency tolerance 45/65 Hz
Power factor 0.93
Current distorsion <5%
Soft start 0-100% in 10"
BY PASS  
Rated voltage 400 Vac three-phase selectable 380 and 415
Voltage tolerance ± 15% (selectable from ± 10% to ± 25% from front panel)
Rated frequency 50/60 Hz (autorange)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Number phases 3
Back-feed protection yes
Overload capacity Inx10ms 14
OUTPUT and INVERTER OUTPUT  
Rated power 30000 VA
Active power 24000 W
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Static stability ± 1%
Dynamic stability ± 5% in 5 ms
Frequency same as the input (autorange)
Voltage distortion with distorcing load <3%
Voltage distortion with linear load 1% (rated) 2% (max)
Frequency stability ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present
Inverter efficiency at rated load 95% %
Overload 125% 150% 200% of the rated current for 10^ / 1^ / 7§
RECTIFIER OUTPUT  
Ripple <1%
BATTERIES  
Type Maintenance-free sealed lead-acid
Maximum recharge current 0.2xC10
ENVIRONMENTAL  
Altitude max 1000 m
Color Light grey RAL 7035
Remote controls EPO and bypass
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Protection rating 3
Cooling (type) redundant fans
AC/AC efficiency 92,5%
Noise 63 dBA at 1 m
Remote signals voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA)
Operating temperature 0 ÷ 40 °C
Relative humidity 95% no condensing
DATA  
Weight 850 Kg
Dimensions (h w d) 1900x800x800 mm


 

Brochure