UPS-urile de seria industrială oferă protecție maximă și energie de calitate pentru orice tip de încărcătură, în special aplicații industriale, cum ar fi fabricația, dar și procesele petrochimice, distribuția electrică și centralele electrice.
Master Industrial este un UPS cu dublă conversie on-line (clasa VFI SS 111 în conformitate cu IEC EN 62040-3) cu transformatoare de izolație de intrare și ieșire.
Technical specifications of the model | MIM 80 |
Models | MIM 80 |
INPUT | |
Rated power | 80000 VA |
Voltage | 400 Vac three-phase Vac |
Voltage tolerance | ± 20% |
Frequency | 50/60 Hz with autorange |
Frequency tolerance | 45/65 Hz |
Power factor | 0.93 |
Current distorsion | <5% |
Soft start | 0-100% in 10″ |
BY PASS | |
Rated voltage | 400 Vac three-phase selectable 380 and 415 |
Voltage tolerance | ± 15% (selectable from ± 10% to ± 25% from front panel) |
Rated frequency | 50/60 Hz (autorange) |
Frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) |
Number phases | 3 |
Back-feed protection | yes |
Overload capacity Inx10ms | 14 |
OUTPUT and INVERTER OUTPUT | |
Rated power | 80000 VA |
Active power | 64000 W |
Number phases | 3 + N |
Crest factor (Ipeak/Irms) | 3 : 1 |
Waveform | Sinewave |
Static stability | ± 1% |
Dynamic stability | ± 5% in 5 ms |
Frequency | same as the input (autorange) |
Voltage distortion with distorcing load | <3% |
Voltage distortion with linear load | 1% (rated) 2% (max) |
Frequency stability | ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present |
Inverter efficiency at rated load | 95% % |
Overload | 125% 150% 200% of the rated current for 10^ / 1^ / 7§ |
RECTIFIER OUTPUT | |
Ripple | <1% |
BATTERIES | |
Type | Maintenance-free sealed lead-acid |
Maximum recharge current | 0.2xC10 |
ENVIRONMENTAL | |
Altitude max | 1000 m |
Color | Light grey RAL 7035 |
Remote controls | EPO and bypass |
Safety compliance | EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU |
EMC conformance | EN 62040-2 and Directive 2014/30/EU |
Protection rating | 3 |
Cooling (type) | redundant fans |
AC/AC efficiency | 92,5% |
Noise | 63 dBA at 1 m |
Remote signals | voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA) |
Operating temperature | 0 ÷ 40 °C |
Relative humidity | 95% no condensing |
DATA | |
Weight | 1500 Kg |
Dimensions (h w d) | 1900x1600x800 mm |
Download PDF