Master MHE 600
Master HE series is available from 100 to 800 kVA. The UPS feature a new on-line double-conversion technology utilising IGBT and DSP (Digital Signal Processor) control to provide maximum protection, power quality and green energy for any type of application including primary datacenters, disaster recover sites, telecoms rooms, industrial processes and security applications.
High efficiency stands for higher active power available if compared with legacy UPS thanks to output unitary p.f. Nominal power is granted with no downgrading indipendently from operating temperature.
Technical specifications of the model | MHE 600 |
Models | MHE 600 |
INPUT | |
Rated power | 600000 VA |
Voltage | 400 Vac three-phase Vac |
Voltage tolerance | + 20% - 25% |
Frequency | 50/60 Hz with autorange |
Frequency tolerance | 45/65 Hz |
Power factor | 0,99 |
Input current | 842 A |
Current distorsion | <3% |
Soft start | 0-100% in 10 |
BY PASS | |
Rated voltage | 400 Vac three-phase selectable 380 and 415 |
Voltage tolerance | ± 15% (selectable from ± 10% to ± 25% from front panel) |
Rated frequency | 50/60 Hz (autorange) |
Frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) |
Rated current | 842 A |
Number phases | 3 |
Back-feed protection | Yes |
Overload capacity Inx10ms | 14 |
OUTPUT and INVERTER OUTPUT | |
Rated power | 600000 VA |
Active power | 600000 W |
Number phases | 3 + N |
Crest factor (Ipeak/Irms) | 3 : 1 |
Waveform | Sinewave |
Dynamic stability | ± 5% in 5 ms |
Frequency | same as the input (autorange) |
Voltage distortion with distorcing load | <3% |
Voltage distortion with linear load | <1% |
Frequency stability | ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present |
Overload | 125% 150% 200% of the rated current for 10' / 1' / 7 |
RECTIFIER OUTPUT | |
Ripple | <1% |
BATTERIES | |
Type | Maintenance-free sealed lead-acid |
Maximum recharge current | 0.2xC10 |
ENVIRONMENTAL | |
Altitude max | 1000 m |
Color | Dark grey RAL 7035 |
Remote controls | EPO and bypass |
Safety compliance | EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU |
EMC conformance | EN 62040-2 and Directive 2014/30/EU |
Protection rating | 3 |
Line-Interactive/Smart Active efficiency | up to 99,4% |
Noise | 70 dBA at 1 m |
Remote signals | voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA) |
Operating temperature | 0 ÷ 40 °C |
Relative humidity | 95% no condensing |
DATA | |
Weight | 2830 Kg |
Dimensions (h w d) | 1900x2100x1000 mm |